Sheath Loss Factors Taking Into Account the Proximity Effect for a Cable Line in a Touching Flat Formation

Abstract

This paper presents the development of a correction coefficient for the International Electrotechnical Commission (IEC) Standard 60287-1-1 formula for the sheath loss factor of the middle cable in a touching flat formation. The solid sheaths are bonded and earthed at both ends of an electrical section. The reason for this correction is to take into account a nonuniform distribution of the losses within each sheath arising from the proximity effect. The coefficient is developed by using the filament method as well as the stochastic optimization algorithm based on differential evolution. The IEC formulae for the sheath loss factors of the outer cables, forming a part of the touching formation, do not need to be modified in order to consider the proximity effect.

Publication
IEEE transactions on power delivery
Nikša Kovač
Nikša Kovač
Full Professor | Department of Electrical Engineering Fundamentals
Tomislav Kilić
Tomislav Kilić
Full Professor | Department of Electrical Measurements

Full professor at the at the Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture in Split, with professional reserch focus on power quality, signal analysis in electrical power systems, and measurement of process variables, alongside a significant role in the academic and administrative life of the University of Split.